INTRUSION&FIRE ALARM ADDRESSABLE 20-LOOP CONTROL DEVICE
22
riod given for this alarm loop. For the executive programs 9 (LAMP), 10
(Alarm output 1), 13 (Fire output), 14 (Output FAULT), 15 (Fire LAMP) and
16 (Alarm output 2) that are documented in Table 5 these parameters are
ignored and relays switch straight after the alarm loop status having been
changed.
4.1.1.11 Fire Loop Requery Blocking
This parameter allows disabling the function of requery of type 1 and
2 loop statuses when single detector has actuated. If the parameter in
question is set on then single detector actuating changes the loop over the
“Fire Prealarm” status.
4.1.1.12 300 ms Integration
This parameter allows giving the resolving time for burglary loops
(types 4, 5, 7, 11). The “switched on” value is corresponded by resolving
time of 300 ms while the “switched off” one is corresponded by those of 70
ms. In order to increase the performance reliability and to decrease the
number of false alarms it is recommended to avoid giving the resolving
time to the 70 s value and to set the parameter under question on.
4.1.1.13 10% Deviation Blocking
This parameter allows disabling the analysis of loop resistance hops
(more than 10% of steady-state value) if they has not yet come out of nor-
mal range for burglary loops (types 4, 5, 7, 11). It is recommended to set
this parameter on if the loop connected detectors generate significant volt-
age ripples at the alarm loop.
Table 3: Loop parameters depending on its status
Loop type Alarm loop statuses
Loop trbl
short
(alarm loop
short
circuit)
Fire alarm
(Actuation of
two or more
smoke de-
tectors)
Fire
prealarm
(
ctuation of
one smoke
detector)
Loop trbl rst
(Loop has
been re-
stored after
any failure)
Loop trbl
open
(alarm
loop
open cir-
cuit)
from 150
Оhм to 1,56
*
kОhм
from 1,1
*
to
1,8 kОhм
1
Fire Smoke
less then
100 Оhм
* Depending on detector
load consumed current
from 2,2 to
5,4 kОhм
above
6,6
kОhм