SIGNAL-20P DESIGN AND OPERATING PRINCIPLES
29
№ Program name Program description Initial
status
15
‘Fire LAMP’ In case of ‘Fire alarm’ switches in inter-
rupted mode (0,25 s ON and 0,25 s OFF)
In case of ‘Fire prealarm’ switches in in-
terrupted mode (0,25 s ON and 0,75 s
OFF)
In cases of ‘Intrusion alarm’, ‘Entry alarm’
or “Arm failed” switches in interrupted
mode (0,5 s ON and 0,5 s OFF)
In case of ‘Fire trouble’ switches in inter-
rupted mode (0,25 s ON and 1,75 s OFF)
If all associated loops are armed
switches output ON
else OFF
*
16
‘Alarm output 2’ If all associated loops are armed or dis-
armed then turns output ON
else turns OFF
*
17
‘Turn on for a given
time before arming’
Turns ON for a given time during arming
delay period
OFF
18
‘Turn off for a given
time before arming’
Turns OFF for a given time during arm-
ing delay period
ON
19
‘Turn on for a given
time when arming’
If at least one loop is armed switches the
relay ON for a given time
OFF
20
‘Turn off for a given
time when arming’
If at least one loop is armed switches the
relay OFF for a given time
ON
21
‘Turn on
for a given time
when disarming’
If at least one loop is disarmed switches
the relay ON for a given time OFF
22
‘Turn off
for a given time
when disarming’
If at least one loop is disarmed switches
the relay OFF for a given time ON
23
‘Turn on for a given
time if arming has
failed’
If at least one loop is in the state ‘Arm
has failed’ switches the relay ON for a
given time
OFF
24
‘Turn off for a given
time if arming has
failed’
If at least one loop is in the state ‘Arm
has failed’ switches the relay OFF for a
given time
ON
25
‘Turn on for a given
time when auxiliary
alarm’
If at least one loop is in the state ‘Auxil-
iary alarm’ switches the relay ON for a
given time
OFF